GE SRTP

Neuron GE SRTP plugin accesses GE PLC devices that support SRTP over TCP.

Parameter Configuration

ParameterDescription
hostPLC IP address
portPLC port, default 18245
timeoutTimeout for sending requests to the device, default 3000 ms

Support Data Type

  • uint8
  • int8
  • uint16
  • int16
  • uint32
  • int32
  • uint64
  • int64
  • float
  • double
  • bit
  • string

ADDRESS

AREA ADDRESS[.BIT][.LEN]

.BIT

Optional, referring to a bit of an address, range 0 - 15.

.LEN

When the data type is a string type, it is required and indicates the length of the string.

ADDRESS AREA

AREADATA TYPEATTRIBUTEPLC AREA
%Iint8/uint8/bitRDiscrete inputs
%Qint8/uint8/bitR/WDiscrete outputs
%Mint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WInternal references
%Tint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WTemporary references
%SAint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WSystem status references A
%SBint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WSystem status references B
%SCint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WSystem status references C
%Sint8/uint8/int32/uint32/int64/uint64/float/double/bitR/WSystem status references
%Gint32/uint32/int64/uint64/float/double/bitR/WDiscrete globals
%AIint32/uint32/int64/uint64/float/double/bitRAnalog input registers
%AQint32/uint32/int64/uint64/float/double/bitR/WAnalog output registers
%Rint32/uint32/int64/uint64/float/double/bit/stringR/WSystem register reference

Address Examples

ADDRESSDATA TYPEDes
%I100bit%I100
%I100uint8%I100~%I107
%Q200bit%Q200
%Q200uint8%Q200~%Q207
%R100int16%R100
%AI100float%AI100 float
%R10double%R10 double
%R100.2bit%R area, the starting data word is 100, bit 2
%R200.12string%R area, the starting data word is 200, a string of 12 characters