Inovance Modbus TCP
Inovance Modbus TCP is a version of the Modbus protocol based on Ethernet, utilizing TCP/IP for communication.
The Neuron Inovance Modbus TCP plugin is tailored for Inovance PLC tags.
Add Device
Go to Configuration -> South Devices, then click Add Device to add the driver. Configure the following settings in the popup dialog box.
Plugin | Description |
---|---|
Inovance Modbus TCP | Modbus TCP protocol implementation, adapted for Inovance PLC points. |
Device Configuration
After clicking Create, you will be redirected to the Device Configuration page, where we will set up the parameters required for Neuron to establish a connection with the device. You can also click the device configuration icon on the southbound device card to enter the Device Configuration interface.
Parameter | Description |
---|---|
Send Interval | The waiting time between sending each read/write command. Some serial devices may discard certain commands if they receive consecutive commands in a short period of time. |
PLC IP Address | The IP address of the device. |
PLC Port | The port number of the device. |
Connection Timeout | The time the system waits for a device to respond to a command. |
Configure Data Groups and Tags
After the plug-in is added and configured, the next step is to establish communication between your device and Neuron by adding groups and tags to the Southbound driver.
Once device configuration is completed, navigate to the South Devices page. Click on the device card or device row to access the Group List page. Here, you can create a new group by clicking on Create, then specifying the group name and data collection interval.
Upon successfully creating a group, click on its name to proceed to the Tag List page. This page allows you to add device tags for data collection. You’ll need to provide information such as the tag address, attributes, and data type.
For information on general configuration items, see Connect to Southbound Devices. The subsequent section will concentrate on configurations specific to the driver.
Data types
- BIT
- INT8
- UINT8
- INT16
- UINT16
- INT32
- UINT32
- INT64
- UINT64
- FLOAT
- DOUBLE
- STRING
- BYTES
Address format
ADDRESS[.BIT][#ENDIAN][.LEN[H][L][D][E]][.BYTES]
TIP
Since communication is done via TCP/IP, the device is searched through the IP address and port number, making it unnecessary to specify the station number in the message. Neuron defaults the station number to 1.
ADDRESS
Required, refers to the register address. HuiChuan PLC supports coil and register access for MODBUS protocol. Different from the standard Modbus protocol, each area’s address range is as follows:
The address areas are divided into two types according to the PLC model.
Small PLCs: EASY series, H5U, etc.
Area | Address Range | Quantity | Attribute | Register Size | Function Code | Data Type |
---|---|---|---|---|---|---|
M0-M7999(Coils) | 0x0000-0x1F3F (0-7999) | 8000 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
B0-B32767(Coils) | 0x3000-0xAFFF (12288-45055) | 32768 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
S0-S4095(Coils) | 0xE000-0xEFFF (57344-61439) | 4096 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
X0-X1777(octal) (Coils) | 0xF800-0xFBFF (63488-64511) | 1024 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
Y0-X1777(octal) (Coils) | 0xFC00-0xFFFF (64512-65535) | 1024 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
D0-D7999(Holding Registers) | 0x0000-0x1F3F (0-7999) | 8000 | Read/Write | 16Bit,2Byte | 0x03,0x06,0x10 | Various |
R0-R32767(Holding Registers) | 0x3000-0xAFFF (12288-45055) | 32768 | Read/Write | 16Bit,2Byte | 0x03,0x06,0x10 | Various |
TIP
The X and Y areas’ addresses are represented in octal.
Medium PLCs: AM series, AC series, etc.
Area | Address Range | Quantity | Attribute | Register Size | Function Code | Data Type |
---|---|---|---|---|---|---|
QX0.0-QX8191.7(Coils) | 0x0000-0xFFFF (0-65536) | 65536 | Read/Write | 1Bit | 0x01,0x05,0x0f | BIT |
MW0-MW65535(Holding Registers) | 0x0000-0xFFFF (0-65536) | 65536 | Read/Write | 16Bit,2Byte | 0x03,0x06,0x10 | Various |
SM0-SM7999 | 0x0000-0x1F3F (0-7999) | 8000 | Read/Write | 16Bit,2Byte | 0x01,0x05,0x0f | BIT |
SD0-SD7999 | 0x0000-0x1F3F (0-7999) | 8000 | Read/Write | 16Bit,2Byte | 0x03,0x06,0x10 | Various |
TIP
The M area supports multiple addressing methods, including MX, MB, MW, MD, which correspond to addressing by bit, Byte, Word, and Dword, respectively. When using MX and MB addressing methods, the tags only support read attributes.
.BIT
Optional, specify a specific bit in a register
Address | Data Type | Description |
---|---|---|
D4.0 | bit | D area, address 4, bit 0 |
D10.4 | bit | D area, address 10, bit 4 |
D1.15 | bit | D area, address 1, bit 15 |
#ENDIAN
Optional, byte order, applicable to data types int16/uint16/int32/uint32/float, see the table below for details.
Symbol | Byte Order | Supported Data Types | Note |
---|---|---|---|
#B | 2,1 | int16/uint16 | |
#L | 1,2 | int16/uint16 | Default byte order if not specified |
#LL | 3,4,1,2 | int32/uint32/float | Default byte order if not specified |
#LB | 4,3,2,1 | int32/uint32/float | |
#BL | 1,2,3,4 | int32/uint32/float | |
#BB | 2,1,4,3 | int32/uint32/float |
TIP
Please note, the default byte order for the Inovance plugin is 3,4,1,2. Therefore, the order represented by the byte order symbol does not conform to the common definition.
.LEN[H][L]
When the data type is STRING, .LEN
is a required field, indicating the number of bytes the string occupies. Each register contains two storage methods: H, L, as shown in the table below.
Symbol | Description |
---|---|
H | One register stores two bytes, with the high byte first |
L | One register stores two bytes, with the low byte first |
TIP
Please note, the default byte order for Inovance plugin strings is L.
.BYTES
Optional, read and write the length of bytes type data, applicable to bytes data type.
TIP
A register of the Modbus driver contains 2 bytes. When reading and writing Modbus register data in the bytes data type, please ensure that the bytes parameter is set to an even number.
Example Addresses
Address | Data Type | Description |
---|---|---|
D4 | int16 | D area, address 4, byte order #L |
D4#L | int16 | D area, address 4, byte order #L |
D4#B | uint16 | D area, address 4, byte order #B |
D4 | int32 | D area, address 4, byte order #LL |
D4#LB | uint32 | D area, address 4, byte order #LB |
D4#BB | uint32 | D area, address 4, byte order #BB |
D4#LL | int32 | D area, address 4, byte order #LL |
D4#BL | float | D area, address 4, byte order #BL |
D1.10 | String | D area, address 1, character length 10, byte order L, which occupies addresses D1 to D5 |
D1.10H | String | D area, address 1, character length 10, byte order H, which occupies addresses D1 to D5 |
D1.10L | String | D area, address 1, character length 10, byte order L, which occupies addresses D1 to D5 |
M8 | bit | M area, address 8 |
X10 | bit | M area, address 8 |
MX1.1 | bit | M area, address is the tenth bit of the first register |
MB1 | int8 | X area, address is the low byte of the first register |
MW1 | int16 | X area, address is the second register |
MD1 | int32 | X area, address is the third register |
Use Case
Using Inovance’ PLC programming software AutoShop, you can quickly connect to the PLC and Neuron for debugging. For specific operations, see Connect to Easy521.
Data Monitoring
After completing the point configuration, you can click Monitoring -> Data Monitoring to view device information and control devices. For details, refer to Data Monitoring.