IEC 60870-5-104 Server Simulator Connection Example

This article will use the IEC60870-5-104 plugin of Neuron to connect to IEC60870-5-104 Server SimulatorConnect to IEC60870-5-104 Server Simulator - 图1 (opens new window), which supports the collection of multiple data types and control.

Download IEC 60870-5-104 Server Simulator

You can download the IEC6087-5-104 Server Simulator from hereConnect to IEC60870-5-104 Server Simulator - 图2 (opens new window), the trial version of the emulator will automatically shut down after 15 minutes of operation, save the configuration data in time. Download and unzip the IEC6087-5-104 Server Simulator executable file, click install.

Simulator configuration

  • Open IEC 60870-5-104 Server Simulator.
  • Click Add Server to create a server.
  • Modify the configuration in table IEC104-SERVER_1, modify the value of the Source IP Address to 0.0.0.0 .
  • In table Configuration_1, click Add Row to create a tag, IEC60870-5 Group to Choose menu selection Measured Normalized, Event Report Type Id menu selection M_ME_NA_1=9.
  • Other parameters keep their default value, IOA default 1, Common Address default 1.

simulator-tag

  • Click Load Configuration and then click Start Communication to run server.

Use Neuron connect simulator

  • Go to Neuron Dashboard, create a south node with IEC60870-5-104 plugin.
  • Click Device Configuration and then Device IP Address fill in the simulator address, other parameters keep default value.
  • Create a group, and then create a tag in that group with tag address 1.
  • In Monitoring -> Data Monitoring page, you can see the tag value after selecting South device and Group name.