Connect to Q03UDE
PLC Setting
Open the GX Works2 PLC programming software and create a new project,
Series
selectQCPU(Q mode)
,Type
selectQ03UDE
,ClickOK
.Click
Connection Destination
->Connection1
->PLC Direct Coupled Setting
->Ethernet
, setAdapter
andIP Address
, ClickOK
.Click on the menu
Online
->Read from PLC
->Select All
->Execute
.Click
Navigation
->Parameter
->PLC Parameter
->Open Setting
,Protocol
selectTCP
,Open System
selectMC Protocol
, SetHost Station Port No.
, ClickEnd
.Click on the menu
Online
->Write to PLC
->Execute
.
Neuron Setting
Add a Mitsubishi 3E device to Neuron Southbound Device Management.
Change the
PLC IP Address
to the target device IP address in the device configuration.Modify
PLC Port
as the target device port in the device configuration and submit the setup form.Add
Group
,Add testtag
.
Test Data List
Name | Address | Attribute | Data type |
---|---|---|---|
DATA1 | D0 | Read Write | INT16 |
DATA2 | D1 | Read Write | UINT16 |
DATA3 | D2 | Read Write | INT32 |
DATA4 | D4 | Read Write | UINT32 |
DATA5 | D6 | Read Write | FLOAT |
DATA6 | D8 | Read Write | DOUBLE |
DATA7 | X0 | Read | BIT |
DATA8 | Y0 | Read Write | BIT |
DATA9 | D20.0 | Read | BIT |
DATA10 | D100.16 | Read Write | STRING |