Connect to FP-XH C30T
Configurator WD
Go to https://www3.panasonic.biz/ac/e/fasys/software\_info/common/tol\_configwd.jsp and download configurator_wd_v177.exe after registration and install it.
Open the Configurator WD software, click on the menu
Option
->Select IP of PC
->Specify the IP address of PC
, select the local IP address and click on theOK
button.Click on the menu
Search
->Search BroadCast
, the FP-X COM5 module will appear in the list.Right click on the FP-X COM5 item in the list and select
Setting IP Address
in the pop-up menu to set a fixed IP address for the PLC device, then clickOK
.Right click on the FP-X COM5 item in the list, select
Communication Setting
in the pop-up menu, set theBaud rate of COM1
to115200
and clickOK
.Right-click on the FP-X COM5 item in the list, select
Communication Setting
->Option Setting
in the pop-up menu, setRespons timeout
to1000
and clickOK
.Open Control FPWIN Pro 7 and confirm that the
Communication Speed
of the PLC serial portCOM1
is115200
.
Neuron Setting
Add a Panasonic Mewtocol device to the Neuron Southbound Device Manager. 2.
Change
PLC IP Address
to the target device IP address in the device configuration. 3.Modify
PLC Port
to be the target device port in the device configuration. 4.Change
Unit Number
to the target device unit number in the device configuration and submit the setup form.
Test Data List
Name | Address | Attribute | Data type |
---|---|---|---|
DATA1 | DT0 | Read Write | INT16 |
DATA2 | DT2 | Read Write | UINT16 |
DATA3 | DT4 | Read Write | INT32 |
DATA4 | DT7 | Read Write | UINT32 |
DATA5 | DT10 | Read Write | FLOAT |
DATA6 | DT13 | Read Write | DOUBLE |
DATA7 | X0 | Read | BIT |
DATA8 | Y0 | Read Write | BIT |
DATA9 | DT20.0 | Read | BIT |
DATA10 | DT17.20 | Read Write | STRING |