Modbus RTU

Modbus RTU is a version of the Modbus protocol that is based on serial communication. Unlike the Modbus TCP protocol, Modbus RTU is typically used to connect sensors, actuators, and other control devices on a factory production line. It is a fast, reliable, and flexible serial communication protocol that provides reliable data transmission and control functions.

The Modbus RTU protocol uses binary encoding and can transmit data over RS-232, RS-485, or other serial communication media. The Modbus RTU plugin for Neuron adds an implementation based on Ethernet TCP and enables remote device data acquisition and control through a DTU device.

Parameters

Parameter Description
Physical Link Selects the communication medium, either serial or Ethernet.
Connection Timeout The time the system waits for a device to respond to a command.
Send Interval The waiting time between sending each read/write command. Some serial devices may discard certain commands if they receive consecutive commands in a short period of time.
Serial Device The path to the serial device when using a serial connection, e.g., /dev/ttyS0 in Linux systems.
Stop Bits Serial connection parameter.
Parity Serial connection parameter.
Baud Rate Serial connection parameter.
Data Bits Serial connection parameter.
Connection Mode When selecting Ethernet TCP connection, you can choose Neuron as the TCP client or server.
IP Address The IP address of the device when using TCP connection with Neuron as the client, or the IP address of Neuron when using TCP connection with Neuron as the server. The default value is 0.0.0.0.
Port The port number of the device when using TCP connection with Neuron as the client, or the port number of Neuron when using TCP connection with Neuron as the server.

Data types

  • INT16
  • UINT16
  • INT32
  • UINT32
  • INT64
  • UINT64
  • FLOAT
  • DOUBLE
  • BIT
  • STRING

Address format

SLAVE!ADDRESS[.BIT][#ENDIAN][.LEN[H][L][D][E]]

SLAVE

Required, Slave is the slave address or site number.

ADDRESS

Required, Address is the register address.The Modbus protocol has four areas, each area has a maximum of 65536 registers, and the address range of each area is shown in the table below. It should be noted that the storage area as large as 65536 is generally not required in practical applications. Generally, PLC manufacturers generally use an address range within 10000. Please pay attention to fill in the correct point address according to the area and function code of the device.

Area Address Range Attribute Register Size Function Code Data Type
Coil 000001 ~ 065536 Read/Write 1Bit 0x01,0x05,0x0f BIT
Input 100001 ~ 165536 Read/Write 1Bit 0x02 BIT
Input Register 300001 ~ 365536 Read/Write 16Bit,2Byte 0x04 BIT,INT16,UINT16,INT32,UINT32,INT64,UINT64,FLOAT,DOUBLE,STRING
Hold Register 400001 ~ 465536 Read/Write 16Bit,2Byte 0x03,0x06,0x10 BIT,INT16,UINT16,INT32,UINT32,INT64,UINT64,FLOAT,DOUBLE,STRING

tip Some device specification documents may use function codes and register addresses to describe commands. Since register address numbers start at 0, the register address range for each area is 0 to 65535. Neuron uses a PLC configuration address specification, so the addresses configured in Neuron start from 1.

The conversion rule for the configuration address specification is as follows: determine the highest digit of the address based on the function code, and add 1 to the register address to obtain the address used in Neuron.

For example, if the function code is 0x03 and the register address is 0, the address used in Neuron is 400001. If the function code is 0x02 and the register address is 5, the address used in Neuron is 100006.

.BIT

Optional, specify a specific bit in a registe

Address Data Type Description
1!300004.0 bit Refers to station 1, input area, address 300004, bit 0
1!400010.4 bit Refers to station 1, hold register area, address 400010, bit 4
2!400001.15 bit Refers to station 2, hold register area, address 400001, bit 15

#ENDIAN

Optional, byte order, applicable to data types int16/uint16/int32/uint32/float, see the table below for details. | Symbol | Byte Order | Supported Data Types | Note | | —- | ———- | ————————— | ——- | | #B | 2,1 | int16/uint16 | | | #L | 1,2 | int16/uint16 | Default byte order if not specified | | #LL | 1,2,3,4 | int32/uint32/float | Default byte order if not specified | | #LB | 2,1,4,3 | int32/uint32/float | | | #BB | 3,4,1,2 | int32/uint32/float | | | #BL | 4,3,2,1 | int32/uint32/float | |

.LEN[H][L][D][E]

When the data type is STRING, .LEN is a required field, indicating the number of bytes the string occupies. Each register contains four storage methods: H, L, D, and E, as shown in the table below. | Symbol | Description | | —- | ——————————————————- | | H | One register stores two bytes, with the high byte first | | L | One register stores two bytes, with the low byte first | | D | One register stores one byte, and it is stored in the low byte | | E | One register stores one byte, and it is stored in the high byte|

Examples

Address Data Type Description
1!300004 int16 Refers to station 1, input area, address 300004, byte order #L
1!300004#B int16 Refers to station 1, input area, address 300004, byte order #B
1!300004#L uint16 Refers to station 1, input area, address 300004, byte order #L
1!400004 int16 Refers to station 1, hold register area, address 400004, byte order #L
1!400004#L int16 Refers to station 1, hold register area, address 400004, byte order #L
1!400004#B uint16 Refers to station 1, hold register area, address 400004, byte order #B
1!300004 int32 Refers to station 1, input area, address 300004, byte order #LL
1!300004#BB uint32 Refers to station 1, input area, address 300004, byte order #BB
1!300004#LB uint32 Refers to station 1, input area, address 300004, byte order #LB
1!300004#BL float Refers to station 1, input area, address 300004, byte order #BL
1!300004#LL int32 Refers to station 1, input area, address 300004, byte order #LL
1!400004 int32 Refers to station 1, hold register area, address 400004, byte order #LL
1!400004#LB uint32 Refers to station 1, hold register area, address 400004, byte order #LB
1!400004#BB uint32 Refers to station 1, hold register area, address 400004, byte order #BB
1!400004#LL int32 Refers to station 1, hold register area, address 400004, byte order #LL
1!400004#BL float Refers to station 1, hold register area, address 400004, byte order #BL
1!300001.10 String Refers to station 1, input area, address 300001, character length 10, byte order L, which occupies addresses 300001 to 300005
1!300001.10H String Refers to station 1, input area, address 300001, character length 10, byte order H, which occupies addresses 300001 to 300005
1!300001.10L String Refers to station 1, input area, address 300001, character length 10, byte order L, which occupies addresses 300001 to 300005
1!400001.10 String Refers to station 1, hold register area, address 400001, character length 10, byte order L, which occupies addresses 400001 to 400005
1!400001.10H String Refers to station 1, hold register area, address 400001, character length 10, byte order H, which occupies addresses 400001 to 400005
1!400001.10L String Refers to station 1, hold register area, address 400001, character length 10, byte order L, which occupies addresses 400001 to 400005
1!400001.10D String Refers to station 1, hold register area, address 300001, character length 10, byte order D, which occupies addresses 400001 to 400005
1!400001.10E String Refers to station 1, hold register area, address 300001, character length 10, byte order E, which occupies addresses 400001 to 400005