Mitsubishi MELSEC A1E
Module Description
The a1e plug-in is used to access Mitsubishi’s A series, FX3U, FX3G, iQ-F series PLCs via Ethernet, iQ-F requires a specific firmware version.
Parameter Configuration
Parameter | Description |
---|---|
host | remote plc ip |
port | remote plc port, default 2000 |
Support Data Type
- INT16
- UINT16
- INT32
- UINT32
- FLOAT
- DOUBLE
- BIT
- STRING
Usage of Address Format
Address Format
AREA ADDRESS[.BIT][.LEN[H][L]]
AREA ADDRESS
AREA | TYPE | ATTRIBUTE | REMARK |
---|---|---|---|
X | bit | read/write | Input relay (FX3/iQ-F) |
Y | bit | read/write | Output relay (FX3/iQ-F) |
M | bit | read/write | Internal relay (FX3/iQ-F) |
L | bit | read/write | Latch relay (FX3/iQ-F) |
F | bit | read/write | Annunciator (FX3/iQ-F) |
B | bit | read/write | Link relay (FX3/iQ-F) |
SB | bit | read/write | Link special relay (FX3/iQ-F) |
S | bit | read/write | (FX3/iQ-F) |
D | all | read/write | Data register (FX3/iQ-F) |
W | all | read/write | Link register (FX3/iQ-F) |
TS | bit | read/write | Timer Contact (FX3/iQ-F) |
TC | bit | read/write | Timer Coil (FX3/iQ-F) |
TN | all | read/write | Timer Current value (FX3/iQ-F) |
STS | bit | read/write | Retentive timer Contact (FX3/iQ-F) |
STC | bit | read/write | Retentive timer Coil (FX3/iQ-F) |
STN | all | read/write | Retentive timer (FX3/iQ-F) |
CS | bit | read/write | Counter Contact (FX3/iQ-F) |
CC | bit | read/write | Counter Coil (FX3/iQ-F) |
CN | all | read/write | Counter Current value (FX3/iQ-F) |
LCS | bit | read/write | Long Counter Contact (FX3/iQ-F) |
LCC | bit | read/write | Long Counter Coil (FX3/iQ-F) |
LCN | all | read/write | Long Counter Current value (FX3/iQ-F) |
SB | bit | read/write | Link special relay (FX3/iQ-F) |
SW | all | read/write | Link special register (FX3/iQ-F) |
SM | bit | read/write | Special relay (FX3/iQ-F) |
SD | all | read/write | Specical register (FX3/iQ-F) |
Z | all | read/write | Index register (FX3/iQ-F) |
LZ | all | read/write | Long Index register (FX3/iQ-F) |
DX | bit | read/write | Link input (FX3/iQ-F) |
DY | bit | read/write | Link output(FX3/iQ-F) |
R | all | read/write | File register (FX3/iQ-F) |
.BIT
It can only be used in non-bit type area, which means to read the specified bit of the specified address, and the binary bit index range is [0, 15].
Address | Data Type | Description |
---|---|---|
D20.0 | bit | D area, address is 20, bit 0 |
D20.2 | bit | D area, address is 20, bit 2 |
.LEN[H][L]
When the data type is string, .LEN indicates the length of the string; H and L can be optional to indicate two byte orders, the default is H byte order.
Address Examples
Address | Data Type | Description |
---|---|---|
X0 | bit | X area, address is 0 |
X1 | bit | X area, address is 1 |
Y0 | bit | Y area, address is 0 |
Y1 | bit | Y area, address is 1 |
D100 | int16 | D area, address is 100 |
D1000 | uint16 | D area, address is 1000 |
D200 | uint32 | D area, address is 200 |
D10 | float | D area, address is 10 |
D20 | double | D area, address is 20 |
D1002.16L | string | D area, address is 1002, string length is 16, endianness is L |
D1003.16 | string | D area, address is 1003, string length is 16, endianness is H |